This year alone, the commercial industry has seen high-profile fires across
the US involving arson, roof solar panel complications, and ammonia refrigeration system
malfunctions. These incidents highlight why commercial warehouses are among the most
challenging property risks to properly evaluate, with each warehouse needing to be
assessed individually based on what it stores and how it operates.
Combustible materials, complex fire protection systems, and industrial refrigeration systems warrant particular attention based on the significant fire and property loss exposures they create. For example, facilities utilizing ammonia refrigeration extend beyond conventional fire protection to include toxic releases, mechanical failures, and substantial business interruption.
Therefore, when assessing these risks, professionals need to consider each commercial warehouse's unique fire hazards, specific sprinkler needs, and industry standards.
Fire Hazards Within the Warehouse Ecosystem
The severity of risk largely depends on the types of commodities
stored, packaging materials, storage configuration, and building construction:
Corrugated cardboard, wood and plastic pallets, and plastics can lead to a rapid
fire. Plastic commodities and expanded foam products can present especially
challenging fire conditions due to their potential heat release and fire
propagation.
The National Fire Protection Association (NFPA) 13, Standard for
the Installation of Sprinkler Systems, provides the primary framework for sprinkler
design and installation. However, a warehouse's fire protection system design must
reflect its actual occupancy and storage conditions. There are multiple factors to
consider, including the following.
Commodity classification and packaging
Maximum storage height and rack configuration
Roof construction
Ignition sources, including electrical equipment, forklifts, and battery
charging stations
Determining Sprinkler System Adequacy
There's a prevalent misconception within the commercial industry that if a facility is equipped with a sprinkler system, then it's automatically adequately protected. The presence of a suppression system doesn't guarantee that a fire would be properly extinguished or controlled if the system was not designed for the current operations, available water supply, storage height, and commodity classification.
NFPA 13 is the technical guidance that must be followed to ensure
the facility is adequately protected, and it outlines exactly what design is
required to ensure the sprinkler system is adequate for the various operations
and/or storage arrangements. NFPA 13 takes into consideration the following.
Maximum storage height (via commodity classification) and ceiling height
Sprinkler type, spacing, and discharge characteristics
Hydraulic calculations and available water supply
In-rack protection
Obstructions, rack flues, and storage clearances
Early Suppression Fast Response (ESFR) systems are mostly used in qualifying high-piled warehouse operations. Unfortunately, ESFR protection is not suitable for every commodity or storage configuration; an unfit example would be a risk requiring in-rack sprinklers.
In addition to NFPA 13, NFPA 25, the Standard for Inspection,
Testing, and Maintenance of Water-Based Fire Protection Systems, must be strictly
followed to ensure the system remains in operating order. Building owners should
maintain documented inspection records, address deficiencies promptly, and implement
formal impairment procedures whenever sprinkler protection is unavailable.
Ammonia Refrigeration Risks and Fire Protection
Ammonia refrigeration is widely used in cold storage facilities
and warehouses because of its favorable refrigeration properties. Unfortunately, its
use presents significant chemical and mechanical hazards. Ammonia is toxic;
corrosive to the eyes, skin, and respiratory system; and flammable under certain
conditions.
In ammonia refrigeration facilities, mechanical integrity is
particularly important. Corrosion, vibration, improper maintenance, and
pressure-related failures could result in an ammonia release. Effective ammonia
safety requires more than installing gas detectors: Facilities must have audible and
visual alarms, emergency ventilation, isolation, and shutdown procedures.
Some of the most significant warehouse-related losses involve multiple exposures. Too often I encounter older facilities where ammonia operations are in the same area as major electrical components or located within a Motor Control Center.
Emergency response procedures should also be coordinated with local fire departments and hazardous-material response resources. A successful risk management program should focus on various areas, including the following.
Verify sprinkler system adequacy. Confirm that the installed sprinkler protection system matches actual commodities, storage heights, rack configurations, and water supply capacities.
Maintain mechanical integrity. Establish documented inspection and mechanical programs for ammonia refrigeration equipment, piping, valves, and pressure relief devices.
Protect against ammonia releases. Evaluate gas detection, ventilation, emergency shutdown, employee training, and evacuation procedures.
Prepare for business interruption. Evaluate refrigeration redundancy, backup power where necessary, alternative cold storage facilities, and inventory recovery plans.
OSHA and NFPA Industry Standards
Several regulatory requirements and industry standards are
particularly important when evaluating warehouse and ammonia refrigeration
operations. Applicable Occupational Safety and Health Administration (OSHA)
requirements vary based on the operation, materials stored, refrigeration system,
and hazards that employees may encounter.
OSHA Requirements
29 CFR 1910.119—Process Safety Management
29 CFR 1910.38—Emergency Action Plan
29 CFR 1910.1200—Hazard Communication
29 CFR 1910.132—Personal Protection Equipment
29 CFR 1910.134—Respiratory Protection, where required
OSHA's Process Safety Management standard generally applies to covered facilities/processes containing 10,000 pounds or more of anhydrous ammonia.
For warehouse fire protection, several NFPA standards are available to address system installation, inspection, testing, and maintenance. Sprinkler systems are only one piece of a completely protected facility; proper pump installation, a robust alarm system, and electrical installations are also vital safeguards for warehouses.
NFPA Standards
NFPA 13: Sprinkler System Design and Installation
NFPA 25: Inspection, Testing, and Maintenance of Sprinkler Systems
NFPA 20: Fire Pump Installation
NFPA 22: Private Fire Protection Water Tanks
NFPA 72: Fire Alarm and Signaling Systems
NFPA 70: Electrical Installations
For industrial ammonia refrigeration, applicable International
Institute of All-Natural Refrigeration and American Society of Heating,
Refrigerating and Air-Conditioning Engineers standards should also be
considered.
Building owners must understand that OSHA regulations,
Environmental Protection Agency requirements, and NFPA standards serve different
purposes. Regulatory obligations and local building codes must be verified for each
facility in operation. Additionally, regularly reviewing the safety measures in
place and the procedures used to maintain them ensures a facility maintains proper
safeguards as operations grow and change.
Conclusion
The bottom line is that an effective risk management system is about understanding how a loss can develop, identifying where protection may fail, and implementing achievable measures to protect people and business operations. Commercial warehouse operations require more than checking a box for sprinkler protection or confirming that an ammonia refrigeration system is operational. The objective is to determine whether the installed safeguards are appropriate for the actual hazards identified and whether the facility has the maintenance procedures, operational controls, and emergency procedures to manage a potential catastrophic event.
Opinions expressed in Expert Commentary articles are those of the author and are not necessarily held by the author's employer or IRMI. Expert Commentary articles and other IRMI content do not purport to provide legal, accounting, or other professional advice or opinion. If such advice is needed, consult with your attorney, accountant, or other qualified adviser.
This year alone, the commercial industry has seen high-profile fires across the US involving arson, roof solar panel complications, and ammonia refrigeration system malfunctions. These incidents highlight why commercial warehouses are among the most challenging property risks to properly evaluate, with each warehouse needing to be assessed individually based on what it stores and how it operates.
Combustible materials, complex fire protection systems, and industrial refrigeration systems warrant particular attention based on the significant fire and property loss exposures they create. For example, facilities utilizing ammonia refrigeration extend beyond conventional fire protection to include toxic releases, mechanical failures, and substantial business interruption.
Therefore, when assessing these risks, professionals need to consider each commercial warehouse's unique fire hazards, specific sprinkler needs, and industry standards.
Fire Hazards Within the Warehouse Ecosystem
The severity of risk largely depends on the types of commodities stored, packaging materials, storage configuration, and building construction: Corrugated cardboard, wood and plastic pallets, and plastics can lead to a rapid fire. Plastic commodities and expanded foam products can present especially challenging fire conditions due to their potential heat release and fire propagation.
The National Fire Protection Association (NFPA) 13, Standard for the Installation of Sprinkler Systems, provides the primary framework for sprinkler design and installation. However, a warehouse's fire protection system design must reflect its actual occupancy and storage conditions. There are multiple factors to consider, including the following.
Determining Sprinkler System Adequacy
There's a prevalent misconception within the commercial industry that if a facility is equipped with a sprinkler system, then it's automatically adequately protected. The presence of a suppression system doesn't guarantee that a fire would be properly extinguished or controlled if the system was not designed for the current operations, available water supply, storage height, and commodity classification.
NFPA 13 is the technical guidance that must be followed to ensure the facility is adequately protected, and it outlines exactly what design is required to ensure the sprinkler system is adequate for the various operations and/or storage arrangements. NFPA 13 takes into consideration the following.
Early Suppression Fast Response (ESFR) systems are mostly used in qualifying high-piled warehouse operations. Unfortunately, ESFR protection is not suitable for every commodity or storage configuration; an unfit example would be a risk requiring in-rack sprinklers.
In addition to NFPA 13, NFPA 25, the Standard for Inspection, Testing, and Maintenance of Water-Based Fire Protection Systems, must be strictly followed to ensure the system remains in operating order. Building owners should maintain documented inspection records, address deficiencies promptly, and implement formal impairment procedures whenever sprinkler protection is unavailable.
Ammonia Refrigeration Risks and Fire Protection
Ammonia refrigeration is widely used in cold storage facilities and warehouses because of its favorable refrigeration properties. Unfortunately, its use presents significant chemical and mechanical hazards. Ammonia is toxic; corrosive to the eyes, skin, and respiratory system; and flammable under certain conditions.
In ammonia refrigeration facilities, mechanical integrity is particularly important. Corrosion, vibration, improper maintenance, and pressure-related failures could result in an ammonia release. Effective ammonia safety requires more than installing gas detectors: Facilities must have audible and visual alarms, emergency ventilation, isolation, and shutdown procedures.
Some of the most significant warehouse-related losses involve multiple exposures. Too often I encounter older facilities where ammonia operations are in the same area as major electrical components or located within a Motor Control Center.
Emergency response procedures should also be coordinated with local fire departments and hazardous-material response resources. A successful risk management program should focus on various areas, including the following.
OSHA and NFPA Industry Standards
Several regulatory requirements and industry standards are particularly important when evaluating warehouse and ammonia refrigeration operations. Applicable Occupational Safety and Health Administration (OSHA) requirements vary based on the operation, materials stored, refrigeration system, and hazards that employees may encounter.
OSHA Requirements
OSHA's Process Safety Management standard generally applies to covered facilities/processes containing 10,000 pounds or more of anhydrous ammonia.
For warehouse fire protection, several NFPA standards are available to address system installation, inspection, testing, and maintenance. Sprinkler systems are only one piece of a completely protected facility; proper pump installation, a robust alarm system, and electrical installations are also vital safeguards for warehouses.
NFPA Standards
For industrial ammonia refrigeration, applicable International Institute of All-Natural Refrigeration and American Society of Heating, Refrigerating and Air-Conditioning Engineers standards should also be considered.
Building owners must understand that OSHA regulations, Environmental Protection Agency requirements, and NFPA standards serve different purposes. Regulatory obligations and local building codes must be verified for each facility in operation. Additionally, regularly reviewing the safety measures in place and the procedures used to maintain them ensures a facility maintains proper safeguards as operations grow and change.
Conclusion
The bottom line is that an effective risk management system is about understanding how a loss can develop, identifying where protection may fail, and implementing achievable measures to protect people and business operations. Commercial warehouse operations require more than checking a box for sprinkler protection or confirming that an ammonia refrigeration system is operational. The objective is to determine whether the installed safeguards are appropriate for the actual hazards identified and whether the facility has the maintenance procedures, operational controls, and emergency procedures to manage a potential catastrophic event.
Opinions expressed in Expert Commentary articles are those of the author and are not necessarily held by the author's employer or IRMI. Expert Commentary articles and other IRMI content do not purport to provide legal, accounting, or other professional advice or opinion. If such advice is needed, consult with your attorney, accountant, or other qualified adviser.